Installation guide
Site Requirements
14
890USE17100 September 2003
Power Supply Selection
Overview In an Advantys island there are at least three connections that need to be supplied
power by an external source:
Logic power connection (to the NIM)
Actuator power connection (to a PDM)
Sensor power connection (to a PDM)
Source power for these can come from one, two or three supplies. Your
requirements are dictated by:
Field devices
Voltage and current needs
Isolation requirements
EMI/RFI suppression needs
CE compliance needs
Cost limitations
The AC voltage for AC PDMs is 85 VAC to 264 VAC
Logic Power You need to supply 24 VDC to your NIM. It converts the 24 VDC to 5 VDC for logic
power across the island bus. Beginning of segment (BOS) modules on additional
segments of your Advantys island need to be supplied their own 24 VDC for logic
power, either from the same supply or an additional one. Either way the supplies that
you select for logic power must have a low voltage limit of 19.2 VDC and a high
voltage limit of 30 VDC.
CAUTION
IMPROPER GALVANIC ISOLATION
The power components are not galvanically isolated. They are intended
for use only in systems designed to provide SELV isolation between the
supply inputs or outputs and the load devices or system power bus. You
must use SELV-rated supplies to provide 24 VDC source power to the
island
Failure to follow this precaution can result in injury or equipment
damage.