Installation guide
Site Requirements
890USE17100 September 2003 13
Inside the Enclosure
Open System
Requirement
To assure performance to specs, open equipment must be installed in an enclosure
that meets NEMA 250 Type 1 requirements and IP 20 requirements conforming to
IEC 529. The enclosure must restrict direct access to qualified service personnel.
Module
Dimensions
The following table describes the width, height , and depth of the standard Advantys
island components.
These depth and height dimensions do not take into account the dimensions of
external power equipment, preferred modules and/or standard CANopen devices.
Thermal
Clearance
For proper heat dissipation, allow a minimum clearance of 100 mm (3.94 in) above
and below each island segment.
Module
size
Width of module
alone
Height of module in
base
Depth of module in base with
field connectors attached
1 13.9 mm (.55 in.) 128.25 mm (5.05 in.) 75.5 mm (2.97 in.)
2 18.4 mm (.73 in.) 128.25 mm (5.05 in.) 75.5 mm (2.97 in.)
2-PDM 18.4 mm (.73 in.) 137.90 mm (5.45 in) 79.5 mm (3.13 in.)
3 28.1 mm (1.11 in.) 128.25 mm (5.05 in.) 70.1 mm (2.76 in)