Specifications

How to Configure the Island
48
EIO0000000051 6/2010
How to Auto-Configure Default Parameters for Island Modules
Introduction
All Advantys STB I/O modules are shipped with a set of predefined parameters that
allow an island to be operational as soon as it is initialized. This ability of island
modules to operate with default parameters is known as auto-configuration. Once
an island bus has been installed, assembled, and successfully parameterized and
configured for your fieldbus network, you can begin using it as a node on that
network.
NOTE: A valid island configuration does not require the intervention of the optional
Advantys Configuration Software.
About Auto-Configuration
Auto-configuration occurs under these circumstances:
z The island is powered up with a factory default NIM configuration. (If this NIM is
subsequently used to create a new island, auto-configuration does not occur
when that new island is powered.)
z You push the RST button (see page 49).
z You force an auto-configuration using the Advantys Configuration Software.
As part of the auto-configuration process, the NIM checks each module and
confirms that it has been properly connected to the island bus. The NIM stores the
default operating parameters for each module in Flash memory.
Customizing a Configuration
In a custom configuration, you can:
z customize the operating parameters of I/O modules
z create reflex actions (see page 230)
z add enhanced CANopen standard devices to the island bus
z customize other island capabilities
z configure communication parameters (STB NIP 2311 only)