Island Status LED Indicators
RUN (green) ERR (red) TEST (yellow) Meaning
blink: 2 blink: 2 blink: 2 The island is powering up (self test in progress).
off off off The island is initializing. The island is not started.
blink: 1 off off The island has been put in the pre-operational state by the RST button.
The island is not started.
blink: 3 The NIM is reading from the removable memory card (see page 56).
on The NIM is overwriting its Flash memory with the card’s configuration
data. (See note 1.)
off blink: 8 off The contents of the removable memory card are invalid.
blinking
(steady)
off off The NIM is configuring (see page 43) or auto-configuring (see page 48)
the island bus. The island bus is not started.
blinking off on Auto-configuration data is being written to Flash memory. (See note 1.)
blink: 3 blink: 2 off Configuration mismatch detected after power up. At least one mandatory
module does not match. The island bus is not started.
off blink: 2 off The NIM has detected a module assignment error; the island bus is not
started.
blink: 5 invalid internal triggering protocol
off blink: 6 off The NIM detects no I/O modules on the island bus.
blinking
(steady)
off The NIM detects no I/O modules on the island bus ... or ...
No further communications with the NIM are possible. Probable causes:
z internal condition
z wrong module ID
z device did not auto-address (see page 44)
z mandatory module is incorrectly configured (see page 227)
z process image is not valid
z device is incorrectly configured (see page 48)
z The NIM has detected an anomaly on the island bus.
z receive/transmit queue software overrun
on off off The island bus is operational.
on blink 3 off At least one standard module does not match. The island bus is
operational with a configuration mismatch.
on blink: 2 off There is a serious configuration mismatch (when a module is pulled from
a running island). The island bus is now in pre-operational mode
because of one or more mismatched mandatory modules.
blink: 4 off off The island bus is stopped (when a module is pulled from a running
island). No further communications with the island are possible.
off on off Internal condition: The NIM is inoperable.
[any] [any] on Test mode is enabled: The configuration software or an HMI panel can
set outputs. (See note 2.)
1 The TEST LED is on temporarily during the Flash overwrite process.
2 The TEST LED is on steadily while the device connected to the CFG port is in control.