Specifications

The STB NIP 2311 NIM Module
26
EIO0000000051 6/2010
The callouts identify the pin numbers for the 8 connectors and the two LEDs:
Communications Cable and Connector
The recommended communications cables are shielded (STP) twisted pair CAT5
electrical cables with shielded RJ-45 connectors. The cables used with the
STB NIP 2311 must terminate with 8-pin male connectors.
The CAT5 cables recommended for connecting the STB NIP 2311 to an Ethernet
LAN have the following characteristics:
NOTE: For technical specifications of CAT5 cables, refer to FCC Part 68, EIA/TIA-
568, TIA TSB-36, and TIA TSB-40.
Pin Description
1tx+
2tx-
3rx+
4 reserved
5 reserved
6rx-
7 reserved
8 reserved
LED NAME Pattern Description
9 LINK (green) blinking or steady on 100Base-T activity: Transmission or
reception of packets with 100Base-T.
LINK (yellow) blinking or steady on 10Base-T activity: Transmission or
reception of packets with 10Base-T.
LINK off No activity: There is no Ethernet traffic.
10 ACT (green) blinking Ethernet link is active.
off Ethernet link is inactive.
standard description max. length application data rate connector to the
fieldbus interface
10Base-T 24-gauge,
twisted pair
100 m (328 ft) data
transmission
10 Mbits/s 8-pin male
100Base-T 24-gauge,
twisted pair
100 m (328 ft) data
transmission
100 Mbits/s 8-pin male
NOTE: There are many 8-pin male connectors that are compatible with the RJ-45 fieldbus
interface on the STB NIP 2311. Refer to the Transparent Factory Network Design and
Cabling Guide for a list of approved connectors.