Specifications

STB NIP 2311 Services
EIO0000000051 6/2010 139
Ethernet Port Diagnostics
Ethernet port diagnostic data can be accessed at the following Modbus register
addresses, relative to the initial address offset value:
Address: Offset + Description
0 port diagnostics data validity
1 logical/physical port number
2 Ethernet control capability
3 link speed capability
4 Ethernet control configuration
5 link speed configuration
6 Ethernet control operational
7 link speed operational
8–10 port MAC address
11–12 media counters data validity
13–14 number of frames transmitted OK
15–16 number of frames received OK
17–18 number of Ethernet collisions
19–20 detected carrier sense errors
21–22 number of Ethernet excessive collisions
23–24 detected CRC errors
25–26 detected FCS errors
27–28 detected alignment errors
29–30 number of detected internal MAC Tx errors
31–32 late collisions
33–34 detected internal MAC Rx errors
35–36 multiple collisions
37–38 single collisions
39–40 deferred transmissions
41–42 frames too long
43–44 frames too short
45–46 detected SQE test error(s)
47 interface counters diagnostic validity
48–49 number of octets received
50–51 number of unicast packets received
52–53 number of non-unicast packets received
54–55 number of inbound packets discard
56–57 number of detected inbound packet errors
58–59 number of unknown inbound packets
60–61 number of octets sent
62–63 number of unicast packets sent
64–65 number of non-unicast packets sent
66–67 number of outbound packets discarded
68–69 number of detected outbound packet errors