Specifications

STB NIP 2311 Services
136
EIO0000000051 6/2010
HMI Registers
The island’s data process image can also be configured to contain:
z HMI output data written from the fieldbus master (usually a PLC) to an HMI
device. This data is stored in registers 44097 to 44608.
z HMI input data written to the fieldbus master from an HMI device. This data is
stored in registers 49488 to 49999.
For more information about the use of these registers, refer to the topic The HMI
Blocks in the Island Data Image (see page 243).
5 link absence (port 2)
6 The NIM has detected at least 1 Ethernet traffic overload condition. This bit is not
reset until the next power cycle.
7 The NIM has recently experienced an Ethernet traffic overload condition. This bit
automatically clears 15 seconds after the register is first read following an overload
condition.
Register 45391 high byte (bits 8-15) (all Advantys STB NIMs)
8 The NIM has detected a module that is not operating.
9 The NIM has detected that at least 1 global bit was set (see page 131).
10 The NIM has detected an external failure on the fieldbus.
11 1 The configuration is password-protected. The RST button is disabled, and the
island configuration requires a password to write to it.
0 The island configuration is in edit mode. The RST button is enabled, and the
configuration is not password-protected.
12 The configuration on the removable memory card is not valid.
13 Reflex action functionality has been configured (for NIMs with firmware version 2.0
or greater).
14 One or more island modules have been hot-swapped (for NIMs with firmware
version 2.0 or greater).
15 1 The Advantys Configuration Software or an HMI panel is controlling the output
data of the island’s process image.
0 Island bus output data master: The fieldbus master device is controlling the
output data of the island’s process image.