Specifications
STB NIP 2311 Services
EIO0000000051 6/2010 131
Error Detection
A value of 1 in any bit in register 45358 indicates that the NIM has detected a global
error condition:
1 No further communications are possible on the island bus.
2 A module has the wrong ID (bit 1): An enhanced CANopen device is using a module ID
reserved for the Advantys STB modules.
3 A device did not auto-address (bit 2).
4 A mandatory module is incorrectly configured (bit 3).
5 The process image is not valid (bit 4): Either the process image configuration is
inconsistent or it could not be set up during auto-configuration.
6 A device is incorrectly configured (bit 5): A module is not in its configured location and the
NIM cannot complete auto-configuration.
7 The NIM has detected an anomaly on the island bus (bit 6).
8 The initialization process in the NIM has detected a module assignment error (bit 7).
9 invalid internal triggering protocol (bit 8).
10 The length of data associated with a module is too long (bit 9).
11 A module is incorrectly configured (bit 10).
Node Configuration
The next 8 contiguous registers (45359 through 45366) display locations where
modules have been configured on the island bus. This information is stored in Flash
memory. At start up, the actual locations of the modules on the island are validated
by comparing them to the configured locations stored in memory. Each bit
represents one configured location:
z A value of 1 in a bit indicates that a module has been configured for the
associated location.
z A value of 0 in a bit indicates that a module has not been configured for the
associated location.