Specifications

Analog Input Modules
92
31007715 6/2008
Averaging You may apply a filter that will smooth the values of the analog inputs reported by
the STB ACI 0320. The Advantys configuration software allows you to average over
a specified number of samples. Averaging is applied on a per-channel basis.
By default, the number samples averaged is one (no averaging); you may have a
filtering average over up to 80 samples. To configure an averaging sample:
This parameter is represented as an unsigned 8-bit number. To access this
parameter using RTP, write the following values to the RTP request block:
Channel
Operation
(Enable/Disable)
The STB ACI 0320 has an input channel enable/disable on a per-channel basis.
You can disable the unused inputs. By default, all inputs are enabled upon auto
configuration. When you disable a channel, its input is set to minimum input current.
The status byte and channel data return all zeros when the channel is disabled, and
the fault indicator does not blink.
z channel enable (default)
z channel disable
8 Save the new configuration parameters. When the configuration is downloaded
to the physical island, the new offset and
maximum count parameters are applied
to the analog input channel and your 4
and 20 mA readings should be 0 and
32 000, respectively.
Step Action Result
Step Action Result
1 Double click the STB ACI 0320 module
you want to configure in the island editor.
The selected STB ACI 0320 module
opens in the software module editor.
2 In the Value column of the Averaging
row, enter a decimal or hexadecimal value
in the range 1 to 80 (0x50).
When you select the Averaging value,
the max/min values of the range appear
at the bottom of the module editor screen.
Length 1
Index (low byte) 0x02
Index (high byte) 0x24
Sub-index 1 for channel 1
2 for channel 2
3 for channel 3
4 for channel 4
Data Byte 1 1 to 80 (0x01 to 0x50)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com