Specifications
Analog Input Modules
31007715 6/2008 63
Averaging You may apply a filter that will smooth the values of the analog inputs reported by
the STB AVI 1270. The Advantys configuration software allows you to average over
a specified number of samples. By default, the number of samples averaged is one
(no averaging); you may a average over up to eight samples. To configure an
averaging sample:
Averaging is applied at the module level, not on a per-channel basis.
This parameter is represented as an unsigned 8-bit number. To access this
parameter using RTP, write the following values to the RTP request block:
6 If adjustments need to be made, take the
Advantys configuration software offline.
7 Double-click on the appropriate
STB AVI 1270 module in the island
editor.
The module editor for the selected
STB AVI 1270 module will open.
8 Open the Properties sheet in the module
editor. In the Offset value field, enter the
data value that you read when 0 V was
applied. In the Max. Count value field,
enter the data value that you read when
10 V was applied.
9 Save the new configuration parameters. When the configuration is downloaded to the
physical island, the new offset and
maximum count parameters will be applied
to the analog input channel.
Step Action Result
Step Action Result
1 Double click on the STB AVI 1270 module
you want to configure in the island editor.
The selected STB AVI 1270 module opens
in the software module editor.
2 In the Value column of the Averaging row,
enter a decimal or hexadecimal value in
the range 1 to 8.
When you select the Averaging value, the
max/min values of the range appear at the
bottom of the module editor screen.
Length 2
Index (low byte) 0x02
Index (high byte) 0x24
Sub-index 0
Data Byte 1 1 to 8