Specifications

Analog Input Modules
31007715 6/2008 57
Field
Wiring Pinout
The top connector supports analog sensor 1, and the bottom connector supports
analog sensor 2. Four field wires may be used on each connector—on pins 1, 3, 4
and 6.
The connections on pin 1 and pin 6 are optional, and using these pins will defeat the
built-in isolation between the analog portion of the module and the island’s sensor
bus. No connections are made on pins 2 and 5 of either connector:
The analog returns (pin 4) for each channel are internally connected—therefore
there is no channel-to-channel isolation.
Sample
Wiring Diagrams
The following field wiring example shows how two single-ended analog sensors can
be wired to the STB AVI 1270 module. An external power supply is required to
power the sensors:
3 inputs from sensor 1 (top) and sensor 2 (bottom)
4 returns from input 1 (top) and input 2 (bottom)
Pin Top Connections Bottom Connections
1 +24 VDC from sensor bus for field
device accessories
+24 VDC from sensor bus for field device
accessories
2 no connection no connection
3 input from sensor 1 input from sensor 2
4 analog input return analog input return
5 no connection no connection
6 field power return (to the module) field power return (to the module)
3
4
3
4
U
+
-
U
+
-
-
+
PE
PE
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com