Specifications

Power Distribution Modules
370
31007715 6/2008
The fuses for the sensor power and actuator power are housed in slots on the right
side of the module:
1 housing door for the 5 A sensor power fuse
2 housing door for the 10 A actuator power fuse
3 notches in the two doors
4 burn hazard statement
The two red plastic doors house a pair of fuses:
z a 5 A fuse protects the input modules on the island’s sensor bus
z a 10 A protects the output modules on the island’s actuator bus
The marking on the side of the module describes a simple precaution you need to
take before replacing a fuse (see p. 377) to prevent burns:
BURN HAZARD - HOT FUSE
Disconnect power for 10 minutes before removing fuse.
Failure to follow these instructions can result in injury or equipment damage.
1
2
3
4
CAUTION