Specifications

Analog Output Modules
31007715 6/2008 363
where C
n
is the numerical count and V
ao
is the analog output voltage.
In an ideal linear voltage representation for +/-10 VDC range, a value of 32 001
represents an OVW. If the output value is less than or equal to -32 001, the module
reports a UVW. When the output value reaches 32 767, an OVE occurs. When the
output value reaches -32 768, a UVE occurs.
An ideal linear voltage representation is interpreted using the formula:
V
ao
= C
n
/3200
where C
n
is the numerical count and V
ao
is the analog output voltage.
32 767
32 001
5.12 V
>5 V
OVE
OVW
-32 768
-32 001
-5.12 V
<-5 V
UVE
UVW
n
ao
V
C
32 767
32 001
10.24 V
>10 V
<-10 V
-10.24 V
-32 768
-32 001
n
ao
V
C
OVE
OVW
UVE
UVW
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com