Specifications
Analog Output Modules
360
31007715 6/2008
Data Formats 0 to 5 VDC and +1 to 5 VDC
In an ideal linear voltage representation for +1 to 5 VDC range, a value of 32 001
represents an OVW. If the output value is less than or equal to - 1, the module
reports a UVW. When the output value reaches 32 767, an OVE occurs. When the
output value reaches - 767, a UVE occurs.
Output voltage (in V) is given by the following formula:
V
ao
= C
n
/8000 + 1
where C
n
is the numerical count and V
ao
is the analog output voltage.
In an ideal linear voltage representation for 0 to 5 VDC range, a value of 32 001
represents an OVW. If the output value is less than or equal to 767, the module
reports a UVW. When the output value reaches 32 767, an OVE occurs. When the
output value reaches 0, a UVE occurs.
An ideal linear voltage representation is interpreted using the formula:
V
ao
= C
n
/6400
Error +1 to 5 VDC Range 0 to 5 VVDC Range
OVE (over voltage error) (32 767)
5.10 VDC
(32 767)
5.12 VDC
OVW (over voltage warning) (32 001)
>5 VDC
(32 001)
>5 VDC
UVW (under voltage warning) (-1)
<1 VDC
(767)
<0.12 VDC
UVE (under voltage error) (-768)
<=0.905 VDC
(0)
0VDC
V
C
ao
n
32 767
32 000
16 000
<1 V
UVW
UVE
0.905 V
-768
3V
>5 V
5.10 V
OVE
OVW