Specifications
Analog Output Modules
354
31007715 6/2008
STB AVO 0200 Field Wiring
Summary The STB AVO 0200 module uses two six-terminal field wiring connectors. Analog
actuator 1 is wired to the top connector, and the analog actuator 2 is wired to the
bottom connector.
Connector Types Use a set of either:
z two STB XTS 1100 screw type field wiring connectors (available in a kit of 20)
z two STB XTS 2100 spring clamp field wiring connectors (available in a kit of 20)
These field wiring connectors each have six connection terminals, with a 3.8 mm
(0.15 in) pitch between each pin.
Field Actuators The STB AVO 0200 module supports two 2-wire analog actuators. It handles analog
outputs ranging from 1to5VDC, 0to5VDC, 0to10VDC, +/-5VDC, or +/-
10 VDC. Data on each channel has a resolution of 15 bits plus sign.
Field Wire
Requirements
Individual connector terminals accept one field wire. Use wire sizes in the range
0.5...1.5mm
2
(24 ... 16 AWG).
Shielded twisted-pair wire is recommended. The shield should be tied to an external
clamp that is tied to functional earth.
We recommend that you strip at least 9 mm from the wire’s jacket for the module
connection.
Field
Wiring Pinout
Pin Top Connections Bottom Connections
1 no connection no connection
2 no connection no connection
3 output to actuator 1 output to actuator 2
4 output channel return output channel return
5 no connection no connection
6 no connection no connection