Specifications
Analog Output Modules
338
31007715 6/2008
Sample
Wiring Diagrams
The actuator may be powered either from a built-in loop supply (24 VDC from the
island’s actuator bus through the output module) or from an external loop supply. For
ease of wiring and cost considerations, we recommend that you use the built-in loop
supply.
When you use a built-in loop supply, the pin assignments differ depending on
whether you wire the actuator as a sink or source load. For a sink load, use pins 1
and 2 on the module’s top connector, with a jumper across pins 4 and 6:
1 +24 VDC loop supply
2 output to actuator
1
2
4
6
I
+
-
FE
sink