Specifications
Analog Output Modules
310
31007715 6/2008
The connections on pin 1 and pin 6 are optional, and using these pins will defeat the
built-in isolation between the analog portion of the module and the island’s sensor
bus. No connections are made on pins 3 and 5 of either connector:
The analog returns (pin 4) for each channel are internally connected—therefore
there is no channel-to-channel isolation.
Sample
Wiring Diagrams
The following field wiring example shows how two isolated single-ended analog
actuators can be wired to the STB ACO 1210 module. Two separate external power
supplies are needed to make sure that the proper current is delivered to each
actuator:
2 outputs to actuator 1 (top) and actuator 2 (bottom)
4 field power returns from actuator 1 (top) and actuator 2 (bottom)
Pin Top Connections Bottom Connections
1 +24 VDC from actuator bus for field
device accessories
+24 VDC from actuator bus for field
device accessories
2 output to actuator 1 output to actuator 2
3 no connection no connection
4 analog output return analog output return
5 no connection no connection
6 field power return (to the module) field power return (to the module)
2
4
2
4
I
+
-
-
+
I
+
-
-
+
FE
FE
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com