Specifications

Analog Output Modules
31007715 6/2008 295
The following field wiring example shows how two isolated analog actuators can be
wired to the STB ACO 0220 module using external power supplies.
2 outputs to actuator 1 (top) and actuator 2 (bottom)
4 loop power returns from actuator 1 (top) and actuator 2 (bottom)
Recommended
Loop Power
Supplies
To guarantee EMC performance, in accordance with European Directives (CE, 89/
336/EEC, EN61131-2:2003) when using an external loop supply, you must use one
of the following Telemecanique power supplies.
z ABL7 RE 2403
z ABL7 RE 2405
z ABL7 RP 2410
While the module will function using any 24 VDC loop supply, we cannot guarantee
the module will comply to the European EMC directive (CE) for operation in a noisy
environment. We strongly recommend that you use the built-in loop supply for this
reason.
2
4
2
4
I
+
+
-
I
+
-
-
+
FE
-
FE
+
source
sink