Specifications
Theory of Operation
31007715 6/2008 27
In this case, the STB PDT 3100 PDM is placed directly to the right of the last
115 VAC module. It terminates the sensor and actuator buses for the 115 VAC I/O
voltage group and initiates new sensor and actuator buses for the 24 VDC modules:
1 115 VAC sensor power signal to the PDM
2 115 VAC actuator power signal to the PDM
3 24 VDC sensor power signal to the PDM
4 24 VDC actuator power signal to the PDM
Each standard PDM contains a pair of time-lag fuses to protect the I/O modules in
the segment. A 10 A fuse protects the output modules on the actuator bus, and a
5 A fuse protects the input modules on the sensor bus. These fuses are user-
replaceable.
Note: When you plan the layout of an island segment that contains a mixture of AC
and DC modules, we recommend that you place the AC voltage group(s) to the left
of the DC voltage group(s) in a segment.
115 V
DAI
PDM
DAI DAI
DAO
DAO DAO
NIM
DDI DDO
24 V
PDM
1
2
3
4