Specifications

Analog Output Modules
270
31007715 6/2008
If you want to use 24 VDC from the island’s field power bus to power the single-
ended analog field devices, use pins 1 and 6 as follows:
1 +24 VDC for actuator 1 (top) and for actuator 2 (bottom)
3 outputs to actuator 1 (top) and actuator 2 (bottom)
4 returns from actuator 1 (top) and actuator 2 (bottom)
6 field power return from actuator 1 (top) and actuator 2 (bottom)
Remember that using pins 1 and 6 defeats the built-in isolation between the analog
portion of the module and the island’s actuator bus.
1
3
4
6
1
3
4
6
U
+
-
U
+
-
FE
FE