Specifications

Analog Output Modules
31007715 6/2008 263
fallback states (when
predefined is the fallback
mode)
default setting 0 V on both channels
user-configurable
settings
1
when the voltage is 0 ... 10 V, integer
values between 0 ... 32 000 on each
channel
when the voltage is -10 ... +10 V, integer
values between -32 000 ... +32 000 on
each channel
addressing requirements two words of output data and two
noncontiguous bytes of configuration data
(for voltage range and fallback state)
actuator bus power for accessories 100 mA/channel @ 30 degrees C
50 mA/channel @ 60 degrees C
over-current protection for accessory power yes
field power requirements from a 24 VDC PDM
power protection time-la fuse on the PDM
agency certifications refer to Advantys STB System Planning
and Installation Guide, 890 USE 171
*ATEX applications prohibit hot swapping-refer to the Advantys STB System Planning and
Installation Guide, 890 USE 171
**Basic NIMs do not allow you to hot swap I/O modules.
***This product supports operation at normal and extended temperature ranges. Refer to the
Advantys STB System Planning and Installation Guide, 890 USE 171 for a complete
summary of cabalities and limitations.
1
Requires the Advantys configuration software.