Specifications

Analog Output Modules
31007715 6/2008 253
If you want to use 24 VDC from the island’s actuator bus to power the analog field
devices, this power can be delivered through the output module. To do this, use pins
1 and 6 as follows:
1 +24 VDC for actuator 1 (top) and for actuator 2 (bottom)
3 outputs to actuator 1 (top) and actuator 2 (bottom)
4 returns from actuator 1 (top) and actuator 2 (bottom)
6 field power return from actuator 1 (top) and actuator 2 (bottom)
Remember that using pins 1 and 6 will defeat the built-in isolation between the
analog portion of the module and the island’s actuator bus.
1
3
4
6
1
3
4
6
U
+
-
U
+
-
PE
PE