Specifications
Analog Input Modules
238
31007715 6/2008
where C
n
is the numerical count and V
ai
is the analog input voltage.
Data Format for 0 to 10 VDC:
In an ideal linear voltage representation for 0 to 10 VDC range (one with default
offset or max count settings (see p. 228)), a value of 32 001 represents an OVW. If
the input value is less than or equal to 767, the module will report a UVW. When the
input value reaches 32 767, an OVE occurs. When the input value reaches 0, a UVE
occurs.
However due to user-configurable offset and max count, if used, an OVW may be
generated before the reported count reaches 32 001. Similarly, the reported count
may be at 32 767, but you may not receive the expected OVE.
An ideal linear representation of analog input voltage (one with default offset and
maximum count) is given by the following formula:
Error 0 to 10 VDC Range
OVE (over voltage error) 10.24 VDC
(32 767)
OVW (over voltage warning) >10 VDC
(32 001)
UVW (under voltage warning) <0.24 VDC
(767)
UVE (under voltage error) 0 VDC
(0)
32 767
>5 V
5.12 V
32 001
0
<0.12 V
OVE
OVW
UVW
UVE
n
ai
V
C
767
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com