Specifications
Analog Input Modules
232
31007715 6/2008
Operating Range 0 to 10 VDC
In the operating range of 0 to 10 VDC if you use the Advantys configuration software
to calibrate an offset of 64 at 0 VDC and a max count of 31 744 at 10 VDC, the
system could be represented as follows:
Offset and RTP:
The offset parameter is represented as a signed 16-bit number. To access it using
RTP, write the following values to the RTP request block:
Maximum Count and RTP:
The maximum count parameter is represented as a signed 16-bit number. To
access it using RTP, write the following values to the RTP request block:
Length 2
Index (low byte) 0x00
Index (high byte) 0x24
Sub-index 1 for channel 1
2 for channel 2
3 for channel 3
4 for channel 4
Data Bytes 2 (high byte) & 1 (low byte) -767 to +76 7 (0xFD01 to 0x2FF)
Length 2
Index (low byte) 0x01
Index (high byte) 0x24
64
32 000
32 767
0V
5V
10 V
10.24 V
31 744