Specifications
Theory of Operation
22
31007715 6/2008
As you plan and assemble the island bus, make sure that you choose and insert the
correct base in each location on the island bus.
I/O Each segment contains a minimum of one Advantys STB I/O module. The maximum
number of modules in a segment is determined by their total current draw on the
5 VDC logic power supply in the segment. A built-in power supply in the NIM
provides 5 VDC to the I/O modules in the primary segment. A similar power supply
built into the BOS modules provides 5 VDC for the I/O modules in any extension
segments. Each of these supplies produce 1.2 A, and the sum of the logic power
current consumed by all the I/O modules in a segment cannot exceed 1.2 A.
The Last Device
on the Primary
Segment
The island bus must be terminated with a 120 Ω terminator resistor. If the last
module on the island bus is an Advantys STB I/O module, use an STB XMP 1100
terminator plate at the end of the segment.
If the island bus is extended to another segment of Advantys STB modules or to a
preferred module (see p. 19), you need to install an STB XBE 1000 EOS bus
extension module in the last position of the segment that will be extended. Do not
apply 120 Ω termination to the EOS module. The EOS module has an IEEE 1394-
style output connector for a bus extension cable. The extension cable carries the
island’s communications bus and auto-addressing line to the extension segment or
to the preferred module.
If the island bus is extended to a standard CANopen device (see p. 18), you need to
install an STB XBE 2100 CANopen extension module in the rightmost position of the
segment and apply 120 Ω termination to island bus after the CANopen extension
module—use the STB XMP 1100 terminator plate. You must also provide 120 Ω
termination on the last CANopen device that is installed on the island bus.
Remember that you cannot use extensions when a basic NIM is in the primary
segment.
STB XBA 2100 18.4 mm (0.72 in) the size 2 base that supports an auxiliary power
supply
STB XBA 2200 18.4 mm (0.72 in) the size 2 base that supports the PDMs
STB XBA 2300 18.4 mm (0.72 in) the size 2 base that supports BOS modules
STB XBA 2400 18.4 mm (0.72 in) the size 2 base that supports EOS modules
STB XBA 3000 28.1 mm (1.06 in) the size 3 base that supports many of the special
modules
Base Model Base Width Advantys STB Modules It Supports