Specifications
Analog Input Modules
228
31007715 6/2008
STB AVI 0300 Functional Description
Functional
Characteristics
The STB AVI 0300 module is a four-channel module that handles analog inputs
from four field sensors operating in the +1to5VDC, 0to5VDC, 0to10VDC, +/-5
VDC, or +/-10 VDC range. The following operating parameters are user
configurable:
z offset
z maximum count
z averaging
z range
z channel operation (enable/disable)
Using the RTP feature in your NIM, you can access the value of the following
parameters:
z offset
z maximum count
z averaging
Refer to the Advanced Configuration chapter in your NIM manual for general
information on RTP.
Offset and
Maximum Count
You may apply an offset value to the low end of the operating voltage range and a
maximum count to the high end of the operating voltage range. This feature allows
you to calibrate the analog input channels to match your field device.
Offset is configured as a signed integer. It may be a decimal or hexadecimal value
in the range -767 to +767(0xFD01 to 0x2FF), representing a voltage offset of:
z +/-0.24VDC when the range is 0to10VDC or +/-10VDC
z +/-0.12 VDC when the range is 0 to 5 VDC or +/-5 VDC
z +/-0.1 VDC when the range is 1 to 5 VDC
By default, the offset on both channels is 0.
Maximum count is configured as a decimal or hexadecimal value in the range
31 233 to 32 767 (0x7A01 to 0x7FFF), representing a voltage offset of:
z +/-0.24VDC when the range is 0to10VDC or +/-10VDC
z +/-0.12 VDC when the range is 0 to 5 VDC or +/-5 VDC
z +/-0.1 VDC when the range is 1 to 5 VDC
By default, the maximum count on both channels is 32 000 (0x7D00).
Offset and maximum count may be applied on each channel independently.
Note: Standard NIMs with firmware version 2.0 or higher support RTP. RTP is not
available in basic NIMs.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com