STB AVI 0300 Field Wiring
Summary The STB AVI 0300 module uses two six-terminal field wiring connectors. Analog
sensors 1 and 2 are wired to the top connector. Analog sensors 3 and 4 are wired
to the bottom connector.The choices of connectors and field wire types are
described below, and some field wiring options are presented.
Connectors Use a set of either:
z two STB XTS 1100 screw type field wiring connectors (available in a kit of 20)
z two STB XTS 2100 spring clamp field wiring connectors (available in a kit of 20)
These field wiring connectors each have six connection terminals, with a 3.8 mm
(0.15 in) pitch between each pin.
Field Sensors The STB AVI 0300 module supports four isolated 2-wire analog sensors. It handles
analog inputs in the following voltage ranges: +1 to 5 VDC, 0 to 5 VDC,
0 to 10 VDC, +/-5 VDC, or +/-10 VDC. Data on each channel has a resolution of 15
bits + sign.
Field Wire
Requirements
Individual connector terminals accept one field wire. Use wire sizes in the range
0.5...1.5mm
2
(24 ... 16 AWG).
Shielded twisted-pair cable is required to meet CE. (See the Advantys STB System
Planning and Installation Guide (890 USE 171) for an illustrated example of an
island segment with an EMC kit making the analog I/O modules CE compliant.) The
shield should be tied to an external clamp that is tied to functional earth.
We recommend that you strip at least 9 mm from the wire’s jacket for the module
connection.
Field
Wiring Pinout
No connections are made on pins 3 and 4 of either connector.
Note: An open circuit in the input cabling causes a voltage with an indeterminate
value to be reported.
Pin Top Connections Bottom Connections
1 voltage in 1+ voltage in 3+
2 voltage in 1 - voltage in 3-
3 no connection no connection
4 no connection no connection
5 voltage in 2+ voltage in 4+
6 voltage in 2- voltage in 4-