Specifications

Analog Input Modules
210
31007715 6/2008
This parameter is represented as an unsigned 16-bit number. To access this
parameter using RTP, write the following values to the RTP request block:
Range You may configure the operating range of the STB AVI 1400 on a per-channel basis.
z +1to5VDC
z 0to5VDC
z 0to10VDC
z +/-5 VDC
z +/-10 VDC
Channel
Operation
(Enable/Disable)
The STB AVI 1400 has an input channel enable/disable on a per-channel basis. You
can disable the unused inputs. By default, all inputs are enabled upon auto
configuration. The status byte and channel data return all zeros when the channel is
disabled, and the fault indicator does not blink.
z channel enable (default)
z channel disable
Length 1
Index (low byte) 0x02
Index (high byte) 0x24
Sub-index 1 for channel 1
2 for channel 2
3 for channel 3
4 for channel 4
5 for channel 5
6 for channel 6
7 for channel 7
8 for channel 8
Data Byte 1 1 to 80 (0x50)
Note: The module detects PDM error and flashes the ERR LED even if all eight
channels are disabled..