Specifications

Analog Input Modules
31007715 6/2008 171
TC
Specifications
US/JIS Pt100 four-wire 50 Ω
two- or three-wire 20 Ω
US/JIS Pt1000 four-wire 500 Ω
two- or three-wire 200 Ω
Ni100 four-wire 50 Ω
two- or three-wire 20 Ω
Ni1000 four-wire 500 Ω
two- or three-wire 200 Ω
Cu10 four-wire 50 Ω
two- or three-wire 20 Ω
absolute
accuracy
(RTD errors
not included)
Pt @ 25° C (77° F) +/- 0.5 degrees C
+/- 0.9 degrees F
Cu @ 25° C (77° F) +/- 2.0 degrees C
+/- 3.6 degrees F
Ni @ 25° C (77° F) +/- 0.5 degrees C
+/- 9.0 degrees F
Pt @ 60° C (140° F) +/- 2.0 degrees C
+/- 3.6 degrees F
Cu @ 60° C (140° F) +/- 4.0 degrees C
+/- 6 degrees F
Ni @ 60° C (140° F) +/- 1.6 degrees C
+/- 1.6 degrees F
* Requires the Advantys configuration software.
temperature unit default degrees C
user configurable* degrees C or degrees F
data resolution increments of 0.1 degree (C or F)
broken wire detection monitored independently on each channel
TC sensor types user-configurable* type J -210 ... +1200 degrees C
-346 ... +2192 degrees F
type K -270 ... +1370 degrees C
-454 ... +2498 degrees F
type E -270 ... +1000 degrees C
-454 ... +1832 degrees F