Specifications
Analog Input Modules
170
31007715 6/2008
RTD
Specifications
agency certifications refer to Advantys STB System Planning and
Installation Guide, 890 USE 171
*ATEX applications prohibit hot swapping-refer to Advantys STB System Planning and
Installation Guide, 890 USE 171
**Basic NIMs do not allow you to hot swap I/O modules.
***This product supports operation at normal and extended temperature ranges. Refer to the
Advantys STB System Planning and Installation Guide, 890 USE 171 for a complete
summary of cabalities and limitations.
1
Requires the Advantys configuration software.
temperature
unit
default degrees C
user configurable* degrees C or degrees F
data resolution increments of 0.1 degree (C or F)
broken wire detection monitored independently on each channel
RTD wiring
types
default three-wire
user configurable* two-, three- or four-wire
typical
conversion
times
three-wire devices @ 50 Hz 340 ms
@ 60 Hz 300 ms
two- or four-wire
devices
@ 50 Hz 200 ms
@ 60 Hz 180 ms
RTD sensor
types
default IEC platinum Pt100 -200 ... +850 degrees C
-328 ... +1562 degrees F
user-configurable* IEC platinum Pt100 and
Pt1000
-200 ... +850 degrees C
-328 ... +1562 degrees F
US/JIS platinum Pt100
and Pt1000
-100 ... +450 degrees C
-148 ... 842 degrees F
copper Cu10 -100 ... +260 degrees C
-148 ... +500 degrees F
nickel Ni100 and
Ni1000
-60 ... +180 degrees C
-76 ... +356 degrees F
maximum
wiring
resistance
IEC Pt100 four-wire 50 Ω
two- or three-wire 20 Ω
IEC Pt1000 four-wire 500 Ω
two- or three-wire 200 Ω
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com