Specifications

Analog Input Modules
31007715 6/2008 169
STB ART 0200 Specifications
Summary Each channel on the STB ART 0200 can be configured independently to support an
RTD sensor, a TC sensor or a mV sensor. The following four tables describe the
module specifications.
General
Specifications
.
description two analog input channels individually
configurable for RTD, thermocouple, or mV
operations
data resolution 15 bits plus sign
conversion method Σ - Δ
operating mode self-scan
module width 13.9 mm (0.58 in)
I/O base STB XBA 1000 (see p. 391)
operating voltage range 19.2 to 30 VDC
bus current consumption 30 mA
nominal sensor bus current consumption 170 mA
hot swapping supported* NIM-dependent**
reflex actions supported
as inputs only
1
isolation field-to-bus 1500 VAC for 1 min
channel-to-channel 500 VDC for 1 min
channel-to-field power supply 500 VDC for 1 min
input protection +/- 7.5 V maximum
input filter single low-pass filter @ nominal 25 Hz
cross-talk between channels not measurable
common mode rejection 50 or 60 Hz (100 dB typical)
differential mode rejection 50 or 60 Hz (60 dB typical)
over-range/under-range margins +/- 2.4%
addressing requirement five words (two/channel plus cold-junction
compensation data)
field power requirements from a 24 VDC PDM
power protection time-lag fuse on the PDM
operating temperature range*** 0 to 60°C
storage temperature -40 to 85°C
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com