Specifications
Analog Input Modules
162
31007715 6/2008
z ORE is over-range error
z ORW is over-range warning
z URW is under-range warning
z URE is under-range error
These are the following thermocouple ranges for type J, R, and S thermocouples for
modules with an SV less than or equal to 1.59.
z ORE is over-range error
z ORW is over-range warning
z URW is under-range warning
z URE is under-range error
J type TC degrees C >/= 1200 1171.9.8 -210 ... +1200 < -205.1 </= -210
degrees F >/= 2192 > 2140.6 -346 ... +2192 < -337.9 </= -346
K type TC degrees C >/= 1370 > 1337.1 -270 ... +1370 < -263.5 </= -270
degrees F >/= 2498 > 2438 -454 ... +2498 < -443.1 </= -454
E type TC degrees C >/= 1000 > 976 -270 ... +1000 < -263.5 </= -270
degrees F >/= 1832 > 1788 -454 ... +1832 < -443.1 </= -454
T type TC degrees C >/= 400 > 390.4 -270 ... +400 < -263.5 </= -270
degrees F >/= 752 > 734 -454 ... +752 < -443.1 </= -454
S type TC degrees C >/= 1768 > 1726.6 -50 ... +1768 < -48.8 </= -50
degrees F >/= 3214.4 > 3139.1 -58 ... +3214 < -56.6 </= -58
R type TC degrees C >/= 1768 > 1726.6 -50 ... +1768 < -48.8 </= -50
degrees F >/= 3214.4 > 3139.1 -58 ... +3214 < -56.6 </= -58
B type TC degrees C >/= 1820 > 1726.6 +130 ... 1820 < 133 </= 130
degrees F >/= 3200 > 3123.2 +266 ... 3200 < 272 </= 266
Input Sensor Type ORE ORW Normal Range URW URE
Input Sensor Type ORE ORW Normal Range URW URE
J degrees C >/= 760 > 741.8 -200 ... +760 < -195.2 </= -200
degrees F >/= 1400 > 1366.4 -328 ... +1400 < -320.1 </= -328
R degrees C >/= 1665 > 1625 -50 ... +1665 < -48.8 </= -50
degrees F >/= 3029 > 3029 -58 ... +3029 < -56.6 </= -58
S degrees C >/= 1665 > 1625 -50 ... +1665 < -48.8 </= -50
degrees F >/= 3029 > 3029 -58 ... +3029 < -56.6 </= -58
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com