Specifications

Analog Input Modules
31007715 6/2008 161
Input
Sensor Type
The input sensor type parameter defines the type of analog field device that each
channel will support. By default, both channels support three-wire IEC Pt100 RTD
sensors. You may change the input sensor type on a per/channel basis to be one of
several types of TC, mV, or RTD devices.
If you are not using a sensor on one of the channels, you may configure it as type
none. If you configure it as a particular sensor type and do not connect a physical
device to the channel, the module will detect a broken wire and flash an error on the
LED. Broken wire detection is not provided for mV sensors.
Use the following procedure to configure the input sensor type:
The 16 available input sensor types are:
Step Action Result
1 Double click on the STB ART 0200 module
you want to configure in the island editor.
The selected STB ART 0200 module
opens in the software module editor.
2 Click on the + sign in front of the Input
sensor type parameter.
Channel 1 and Channel 2 are
displayed.
3 In the Value column, select the desired
sensor type from the pull-down menu.
The menu gives you 16 choices, as
listed below.
4 Repeat step 3 if you want to configure a
sensor type for the other channel.
Input Sensor Type ORE ORW Normal Range URW URE
none N/A N/A N/A N/A N/A
+/- mV >/= 81.92 > 80 -80 ... +80 < -80 </= -81.92
Pt100 RTD
(IEC)
degrees C >/= 850 > 829.6 -200 ... +850 < -195.2 </= -200
degrees F >/= 1562 > 1524.5 -328 ... +1562 < -320.1 </= -328
Pt1000 RTD
(IEC)
degrees C >/= 850 > 829.6 -200 ... +850 < -195.2 </= -200
degrees F >/= 1562 > 1524.5 -328 ... +1562 < -320.1 </= -328
Pt100 RTD
(US/JIS)
degrees C >/= 450 > 439.2 -100 ... +450 < -97.6 </= -100
degrees F >/= 842 > 821.8 -148 ... +842 < -144.4 </= -148
Pt1000 RTD
(US/JIS)
degrees C >/= 450 > 439.2 -100 ... +450 < -97.6 </= -100
degrees F >/= 842 > 821.8 -148 ... +842 < -144.4 </= -148
Ni100 RTD degrees C >/= 180 > 175.7 -60 ... +180 < -58.6 </= -60
degrees F >/= 356 > 347.5 -76 ... +356 < -74.2 </= -76
Ni1000 RTD degrees C >/= 180 > 175.7 -60 ... +180 < -58.6 </= -60
degrees F >/= 356 > 347.5 -76 ... +356 < -74.2 </= -76
Cu10 RTD degrees C >/= 260 > 253.8 -100 ...+260 < -97.6 </= -100
degrees F >/= 500 > 488.0 -148 ...+500 < -144.4 </= -148
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com