Specifications

Analog Input Modules
158
31007715 6/2008
Wiring a TC
with External
Cold-junction
Compensation
When you apply external cold-junction compensation (see p. 163) to the module,
you must use a two-wire RTD and connect it to pins 2 and 5 on the top connector.
For optimum results, connect copper wires to pins 2 and 5 on the top connector and
run them to an isothermal terminal block. Make the TC wiring connection to the
terminal block and embed the RTD in the terminal block:
Cold-junction compensation is configured at the module level, and therefore it
applies to any TC sensor(s) connected to the top and/or bottom connector on the
STB ART 0200 module.
Note: When external cold-junction compensation is applied to the module, you may
configure channel 1 to support a TC or mV sensor, but you should not configure it
to support an RTD that senses process values.