Specifications

Analog Input Modules
31007715 6/2008 155
Field
Wiring Pinout
The top connector supports sensor 1, and the bottom connector supports sensor 2.
No connections are ever made on pin 1 of either connector:
Note: Successful operation of the STB ART 0200 is determined by both the way
the module is configured and the way it is field-wired. If you configure a channel to
operate with one type of analog sensor (thermocouple, RTD or mV), you must also
make the proper field connections to make the channel work properly. Similarly,
you need to make sure that the module’s configuration matches the field wiring.
For example, if you have configured a channel to work with a thermocouple and
have field-wired the module correctly, the channel will work properly. If you then
disconnect the TC wiring, the module will detect a broken wire and stop
communicating with that channel. If you then attempt to rewire the channel to
support a different sensor type without changing the configuration, the module will
not detect the new sensor.
Pin Top Connections Bottom Connections
1 no connection no connection
2 Always used for RTD + Always used for RTD +
RTD + connection for external cold-junction
compensation on a TC sensor
no connection for TC or mV no connection for TC or mV
3 TC + or mV + connection TC + or mV + connection
Either used or jumpered for a two-, three-, or
four-wire RTD
Either used or jumpered for a two-,
three-, or four-wire RTD
4 TC - or mV - connection TC - or mV - connection
Either used or jumpered for a two-, three-, or
four-wire RTD
Either used or jumpered for a two-,
three-, or four-wire RTD
5 Always used for RTD - Always used for RTD -
RTD - connection for external cold-junction
compensation on a TC sensor
no connection for TC or mV no connection for TC or mV
6 inner double-shield cable cable shield