Specifications

Analog Input Modules
31007715 6/2008 139
For example, if you use the Advantys configuration software to calibrate an offset
of +64 at 4 mA and a max count of 31 744 at 20 mA, the system could be
represented as follows:
Here are some current representations after calibration with offset and max count:
Offset and RTP:
The offset parameter is represented as a signed 16-bit number. To access it using
RTP, write the following values to the RTP request block:
I
ai
Uncalibrated Calibrated
signed data unsigned data signed data unsigned data
4 mA 64 128 64 128
20 mA 31 744 63 488 31 744 63 488
Length 2
Index (low byte) 0x00
Index (high byte) 0x24
Sub-index 1 for channel 1
2 for channel 2
3 for channel 3
4 for channel 4
Data Bytes 2 (high byte) & 1 (low byte) -767 to +767
64
32 000
32 767
4mA
12 mA
20 mA
20.38 mA
31 744
c
a
l
i
b
r
a
t
e
d
un
c
alib
r
at
e
d
V
n
I
ai