Here are some current representations after calibration with offset and max count:
Offset and RTP:
The offset parameter is represented as a signed 16-bit number. To access it using
RTP, write the following values to the RTP request block:
Maximum Count and RTP:
The maximum count parameter is represented as a signed 16-bit number. To
access it using RTP, write the following values to the RTP request block:
I
ai
Uncalibrated Calibrated
0mA 64 0
5 mA 7984 8000
10 mA 15 904 16 000
15 mA 23 824 24 000
20 mA 31 744 32 000
Length 2
Index (low byte) 0x00
Index (high byte) 0x24
Sub-index 1 for channel 1
2 for channel 2
Data Bytes 2 (high byte) & 1 (low byte) -8191 to +8191
Length 2
Index (low byte) 0x01
Index (high byte) 0x24
Sub-index 1 for channel 1
2 for channel 2
Data Bytes 2 (high byte) & 1 (low byte) 23800 to 32767