Characteristics
Advantys
™
STB Distributed I/O
Solution 0
Phaseo
®
Regulated Power Supplies
(1) Compatible input voltage, not indicated on the product.
Technical characteristics
Type of power supply ABL 7RE ABL 7RP
Approvals
UL, CSA, TÜV, CTick
Conformity to
standards
Security
UL 508, CSA 22.2 no. 950
EMC
EN 50081-1, IEC 61000-6-2 (EN 50082-2)
Low frequency harmonic currents
– EN 61000-3-2
Input circuit
LED indication Orange LED Orange LED
Input voltages Rated values
V a 100…240 a 100…240,
c 110…220 compatible (1)
Permissible voltages
V a 85…264 single-phase a 85…264,
c100…250 compatible (1)
Permissible frequencies
Hz 47…63
Efficiency at nominal load
> 85%
Current consumption Ue = 240 V
A 0.6 (48 W)/0.83 (72 W)
1.2 (120 W)/2.5 (240 W)
0.4 (72 W)/0.6 (120 W)
1.3 (240 W)
Ue = 100 V
A 1.2 (48 W)/1.46 (72 W)
1.9 (120 W)/3.6 (240 W)
0.8 (72 W)/1 (120 W)/2.8 (240 W)
Current at switch-on
A < 30
Power factor
0.65 approx. 0.98 approx.
Output circuit
LED indication Green LED Green LED
Nominal output voltage (U out)
V c 24 12, 24 and 48
Nominal output current
A 2/3/5/10 2,5/5/10
Accuracy Output voltage
Adjustable from 100 to 120%
Line and load regulation
± 3%
Residual ripple - interference
mV < 200 (peak-peak)
Micro-breaks Holding time at I max and Ve min
ms > 10 > 20
Temporary
overloads
Permissible inrush current
(U out >19V)
See page 101
Protection
against
Short-circuits
Permanent/automatic restart Permanent/automatic restart or restart after
switching off mains power
Overload
1.1 In
Overvoltage
Tripping if U > 1.5 Un
Undervoltage
Tripping if U < 0.8 Un
Operational and environmental characteristics
Connections Input mm
2
2 x 2.5 (0.078 x 0.098")+ ground
Output
mm
2
2 x 2.5 (0.078 x 0.098") + ground, multiple output, depending on model
Ambient
conditions
Storage temperature
°C (°F) - 25… + 70 (- 77… + 158)
Operating temperature
°C (°F) 0… + 60 (32… + 140); derating as from 50°C (122°F), mounted vertically
Max. relative humidity
95% without condensation
Degree of protection
IP 20 conforming to IEC 529
Vibrations
Conforming to EN 61131-2
Operating position
Vertical
MTBF at 40°C (104°F)
> 100,000 h
Connections Serial
Possible
Parallel
Possible, max. temperature 50°C (122°F)
Dielectric
strength
Input/output
3000 V/50 and 60 Hz 1 minute
Input/ground
3000 V/50 and 60 Hz 1 minute
Output/ground (and output/output)
500 V/50 and 60 Hz 1 minute
Input fuse incorporated
Yes, not interchangeable
Disturbance
EN 50081-1
Conducted
EN 55011/EN 55022 cl.B
Radiated
EN 55011/EN 55022 cl.B
Immunity
IEC 61000-6-2 (generic)
Electrostatic discharge
EN 61000-4-2 (4 kV contact/8 kV air)
Electromagnetic
EN 61000-4-3 lev.3 (10 V/m)
Conducted interference
EN 61000-4-4 lev.3 (2 kV), EN 61000-4-5, EN 61000-4-6 lev.3, EN 61000-4-8 lev. 4.
Mains interference
EN 1000-4-11 (voltage drops and cuts)