Installation guide

95
Combinations (continued)
Advantys
STB Distributed I/O
Solution 0
High-density I/O modules and Advantys
Telefast
®
ABE 7 cabling system
Module connections STB DDI 3725 - TSX CDP p01
The inputs must be powered via the Advantys STB DDI 3725 module. (1)
Important:
STB DDI 3725 TSX CDP p01 STB DDI 3725 TSX CDP p01
Left
connector
Channel HE 10 Right
connector
Channel HE 10
A IN B IN
Terminal no. Terminal no. Color of wire Terminal no. Terminal no. Color of wire
1 PDM V1 + (1) 17 (2) White-gray 1 PDM V1 + (1) 19 (2) White-pink
2 I1 1 White 2 I9 9 Black
3 3
4 I2 2 Brown 4 I10 10 Violet
5 5
6 I3 3 Green 6 I11 11 Gray-pink
7 7
8 I4 4 Yellow 8 I12 12 Red-blue
9 PDM V1 - 18 (3) Gray-brown 9 PDM V1 - 20 (3) Pink-brown
10 10
11 I5 5 Gray 11 I13 13 White-green
12 12
13 I6 6 Pink 13 I14 14 Brown-green
14 14
15 I7 7 Blue 15 I15 15 White-yellow
16 16
17 I8 8 Red 17 I16 16 Yellow-brown
18 18
(1) Wires 17 and 19 of cable TSX CDP
p
01 (terminals 1 of connectors on STB DDI 3725)
should only be connected if the following two conditions are met:
- no external power supply connected to the Telefast ABE 7 base
- consumption does not exceed 50 mA per group of 4 channels
(2) terminals 17 and 19 of the HE10 connected inside the ABE 7 base
(3) terminals 18 and 20 of the HE10 connected inside the ABE 7 base
Module connections STB DDO 3705 - TSX CDP p01
The outputs must be powered via the Advantys Telefast ABE 7 base.
Important:
STB DDO 3705 TSX CDP p01 STB DDO 3705 TSX CDP p01
Left
connector
Channel HE 10 Right
connector
Channel HE 10
A OUT B OUT
Terminal no. Terminal no. Color of wire Terminal no. Terminal no. Color of wire
1 OUT 1 1 White 1 OUT 9 9 Black
2 PDM V - 20 (1) Pink-brown 2 PDM V - 18 (1) Gray-brown
3 OUT 2 2 Brown 3 OUT 10 10 Violet
4 4
5 OUT 3 3 Green 5 OUT 11 11 Gray-pink
6 6
7 OUT 4 4 Yellow 7 OUT 12 12 Red-blue
8 8
9 NC 9 NC
10 OUT 5 5 Gray 10 OUT 13 13 White-green
11 11
12 OUT 6 6 Pink 12 OUT 14 14 Brown-green
13 13
14 OUT 7 7 Blue 14 OUT 15 15 White-yellow
15 15
16 OUT 8 8 Red 16 OUT 16 16 Yellow-brown
17 17
18 NC 18 NC
NC: Not connected
(1) terminals 18 and 20 of the HE10 connected inside the ABE 7 base