Installation guide
92
Combinations (continued)
Advantys
™
STB Distributed I/O
Solution 0
High-density I/O modules and Advantys
™
Telefast
®
ABE 7 cabling system
Using the Advantys Telefast ABE 7 cabling system rationalizes and simplifies the
cabling of enclosures.
Far less space is required in the enclosure and the Advantys Telefast ABE 7 base
replaces the connection terminals at the bottom of the enclosure.
The Advantys Telefast ABE 7 prewiring system also provides a simple high-density
logic I/O solution for the following voltages:
bc 24 V.
bc 48 V and a 48 V.
ba 110 V.
ba 230 V.
1 Advantys STB I/O island incorporating a high-density module STB DDI 3725
and/or STB DDO 3705.
2 18-pin connector STB XTS 1180 (screw type) or STB XTS 2180 (spring type).
3 Prewired cable TSX CDP 301 (length 3 meters), TSX CDP 501 (length 5 meters)
or TSX CDP 1001 (length 10 meters), with HE 10 connector at one end, flying
leads at other end.
Cross-section 0.324 mm
2
(0.012"
2
), AWG 24.
4 Advantys Telefast ABE 7 connector or adapter base, see compatibility table
opposite.
Note: For further information about the Advantys Telefast ABE 7 prewiring system, see our
catalog “Interfaces, I/O splitter boxes and power supplies.”
Using the Advantys Telefast ABE 7 cabling system
1
2
3
4