Installation guide
75
Characteristics,
catalog numbers
Advantys
™
STB Distributed I/O
Solution 0
Parallel interface module STB EPI 1145
Tego
®
Power applications
(1) A template for the customizing labels is supplied with the documentation mini-CD-ROM.
(2) For other Tego Power components, refer to our catalog: “Motor-starter solutions, control and
power protection components.”
(3) For a set of 8 motor-starters, use 2 x APP 2R4E splitter boxes.
Characteristics
Electrical characteristics
Type of module STB EPI 1145
Swapping Cold swap
Yes
Hot swap
Yes, depending on NIM and obligatory nature of module. See table on page 41
Connection
Via 1 HE 10 connector (30 contacts)
Power supply
Via STB PDT 3100/3105 c 24 V power distribution module
Protection
Via STB PDT 3100/3105 power distribution module fuse
Consumption On c 5 V logic bus
mA up to 110
On c 24 V sensor bus
mA up to 100
On c 24 V actuator bus
mA at least 50 (with all 8 outputs at state 0), up to 1,000 (with all 8 outputs at state 1)
Input characteristics
Number 16 (8 for the status of each contactor/8 for the status of each circuit-breaker)
Nominal values Voltage
c V 24
Limit values At state 1 Voltage
V 15...30
Current
mA at least 2
At state 0 Voltage
V - 3...+ 5
Current
mA up to 0.5
Protection
Resistor-limited
Output characteristics
Number 8 (8 to control each contactor)
Nominal values Voltage
c V 24
Current
mA 100 per channel, 850 per module
Limit values Permanent voltage
V 19.2...30
Absolute voltage
V 36
Peak voltage
A 1 for 100 μs per channel
Max. loads Capacity
μF 50
Inductance
0.5 Henry at 4 Hz
Short circuit and overload protection
Yes, per channel
Catalog numbers
Parallel interface for TeSys
®
motor-starters with Tego Power system
Type of power
supply
Voltage Catalog number Weight
kg
c 24 V STBEPI1145 0.120
STB EPI 1145STB XBA 2000
Obligatory separate parts
Designation Use Length Catalog number Weight
kg
Base 18.4 mm
(0.72")
Application-specific
module mounted on
DIN rail
– STBXBA2000 0.024
Connection cables
(30-pin at each end)
From power and control
splitter box APP 2RpE
to module STB EPI 1145
1 m (1.09 yd) STBXCA3002 –
2 m (2.18 yd) STBXCA3003 –
Obligatory separate Tego Power parts (2)
Designation Use Catalog number Weight
kg
Power and control
splitter boxes
2 outputs APP2R2E –
4 outputs (3) APP2R4E –
Optional separate parts
Designation Use Sold in lots of Catalog number Weight
kg
Keying pin For application-specific
module
60 STBXMP7700 –
Sheets of
customizing
labels (1)
I/O bases and modules 25 STBXMP6700 –
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com