Installation guide

74
Presentation,
description
Advantys
STB Distributed I/O
Solution 0
Parallel interface module STB EPI 1145
Tego
®
Power applications
The STB EPI 1145 parallel interface is a component of the Advantys STB island
designed for the remote connection of 8 motor-starters (or 4 motor-starters in both
directions). These TeSys
®
Model D motor-starters use the Tego Power installation
assistance system.
Tego Power is a modular system to help install TeSys
®
Model D motor-starters by
offering prewired control and power circuits. This Quickfit technology enables cable-
free connections to spring-loaded terminals for TeSys
®
Model D contactors (9 to 25
A) and GV2 M2 motor circuit-breakers.
Tego Power with Quickfit technology enables you to create motor-starter assemblies
up to 15 kW/400 V.
The Tego Power system differentiates the power section from the control section:
b The power kit comprises:
v a specific plate used to assemble 2 to 8 motor-starters.
v two connection modules.
v a power splitter box with a power terminal block.
The contactor for each motor-starter is activated by one of the 8 outputs of the
STB EPI 1145 parallel interface.
b The control kit comprises:
v a control splitter box for the 2 to 8 motor-starters.
v a connection module.
The 2 return outputs of each motor-starter (contactor status, circuit-breaker status)
are connected to 2 of the 16 inputs to the STB EPI 1145 parallel interface.
The STB EPI 1145 parallel interface comprises:
1 A display block with 8 LEDs indicating the state of the various motor-starters or
output devices.
2 A location for a customizing label.
3 A color-coded module identification stripe (black).
4 A selection switch used to view each motor-starter state.
5 An HE 10 connector (30-pin) to connect to a Tego Power system via
STB XCA 3002/3003 cables, length 1 m/2 m (1.09/2.18 yd).
To be ordered separately:
b STB XBA 2000 base width 18.4 mm (0.06"). Includes a location for a customizing
label.
b Optional mechanical keying pin between module and base STB XMP 7700. This
device ensures that the module and its base are properly matched after dismantling
or replacement.
b Sheets of customizing labels: STB XMP 7600.
b A cable between module STB EPI 1145 and the Tego Power block
(1) RDY is on permanently if the module is operational. If RDY is not lit, the PDM is not supplying
power. If RDY flashes, the module is faulty.
(2) If ERR is lit or flashing, the module has an internal error.
For information about the signaling of module and channel states, consult the
System
hardware components reference guide
included on the CD-ROM STB SUS 8800 or available
from our website www.us.telemecanique.com
.
(3) S1: output bank 1 (outputs 1 to 4).
S2: output bank 2 (outputs 5 to 8).
Presentation
1
2
3
4
The Tego Power System
Structure of the Tego Power system
Description
Indication Standard STB EPI 1145 module
Module status (1) Green RDY LED
Module error (2) Red ERR LED
Switch position 4 (3) Green S1 and S2 LEDs
State of outputs Green LEDs O1/5, O2/6, O3/7, O4/8
1
2
4
5
3
1 63 A power splitter box.
2 Control splitter box.
3 Connection cable.
4 Connection control module.
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com