Installation guide
71
Characteristics
Advantys
™
STB Distributed I/O
Solution 0
Parallel interface module STB EPI 2145
TeSys
®
Model U and TeSys
®
Quickfit Applications
Characteristics
Type of module STB EPI 2145
Cold swapping
Yes
Hot swapping
Yes, depending on NIM and mandatory nature of module. See table on page 41
Connection
Via 4 RJ45 connectors
Power supply
Via STB PDT 3100/3105 c 24 V power distribution module
Protection
Via STB PDT 3100/3105 power distribution module fuse
Consumption On c 5 V logic bus
mA up to 110
On c 24 V sensor bus
mA up to 100
On c 24 V actuator bus
mA at least 50 (with all 8 outputs at state 0), 80 mA per output at state 1 (up to 220 mA for 150 ms)
Input characteristics
Number 12
Nominal values Voltage
c V 24
Limit values At state 1 Voltage
V 15...30
Current
mA at least 2
At state 0 Voltage
V - 3...+ 5
Current
mA up to 0.5
Protection
Resistor-limited
Output characteristics
Number 8
Rated voltage
c V 24
Starter-controller compatibility
TeSys Model U 12 A (LUB 12 base) and 32 A (LUB 32 base).
TeSys bases can be fitted with one of the following c 24 V control units:
- standard LUCAppBL.
- advanced LUCBppBL, LUCCppBL and LUCDppBL.
- multifunction LUCAppBL.
Motor-starter compatibility
With TeSys Quickfit prewiring components, components with spring-type terminals. Systems for
motor-starters, from 0 to 25 A, up to 11 kW/400 V.
The motor-starters concerned are those realized by combining:
- GV2 ME circuit-breakers, with use limit at 80% of maximum current at ambient temperature
of 60°C (140°F), up to 690 V standard LUCAppBL.
- with contactors TeSys
®
Model D (LC1) from 9 to 25 A.
- with TeSys Quickfit LAD9 AP3pp control connection module and LU9Rpp cables.
Short circuit and overload protection
Yes, per channel