Installation guide
70
Description (continued)
Advantys
™
STB Distributed I/O
Solution 0
TeSys
®
Quickfit for motor-starter components
TeSys Quickfit is a modular system which standardizes and simplifies the
installation of motor-starters.
Combined with circuit-breakers GV2 ME and TeSys
®
Model D contactors (LC1) from
9 to 25 A, TeSys Quickfit facilitates the installation of motor-starters with spring-type
terminal up to 11 kW/400V.
TeSys Quickfit offers prewiring elements:
b power circuits
b control circuits
Installation of a motor-starter become quick, easy, reliable and open-ended.
TeSys Quickfit also:
b allows later customization of the motor-starter,
b reduces maintenance time and
b saves space inside the equipment by reducing the number of terminals, channels
and intermediate interfaces.
The TeSys Quickfit components for the prewiring of the power section are:
b a power kit comprising, for each output, a mounting plate 1 for the contactor 2 and
circuit-breaker 3 and two power connection modules, 4a and 4b.
b a power splitter 5 for 2 or 4 outputs,
b an upstream terminal block 6 for connecting a power supply up to 60 A (16 mm
2
[0.63"
2
] / # 5 AWG),
b a downstream terminal block 7 for connection of motor power supply cables and
ground cables (6 mm
2
[0.23"
2
] / # 10 AWG).
For the prewiring of the control section, the TeSys Quickfit systems offers a control
connection module 8 LAD 9 AP3pp which allows you to connect the motor outputs
to the processing unit (PLC) via the parallel interface module 9 Advantys
STB EPI 2145, quickly and without tools.
The control connection module LAD 9 AP3pp is mounted directly on the contactor
and the circuit-breaker of each motor-starter. It integrates the status and control
information of this motor-starter.
A mechanical locking device 2 for the system on the head of the contactor
guarantees a satisfactory connection whatever the conditions of use
(vibration, shock etc.). 4 versions are available: for direct or reversing start,
with or without contactor coil interface relay.
The module LAD9 AP3 pp has several external connectors in its lower part including
an RJ45 socket for connection to the Advantys STB EPI 2145 parallel interface
module via LU9Rpp RJ45 cables 10, available in different lengths.
The following information is available for each motor-starter:
b 2 inputs: status of circuit-breaker and status of contactor,
b 1 output: contactor coil control.
A direct motor-starter uses 1 RJ45 channel.
A reversing motor-starter uses 2 RJ45 channels.
(1) See our catalog “motor-starter solutions. Motor control and protection components”.
TeSys Quickfit components for motor-starters
Elements for the prewiring of the power section
12
3
5
6
4a
4b
78
Elements for the prewiring of the control section
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com