Installation guide
68
Description
Advantys
™
STB Distributed I/O
Solution 0
Parallel interface module STB EPI 2145
TeSys
®
Model U and TeSys
®
Quickfit Applications
The application-specific, parallel interface module STB EPI 2145 is a component
of the Advantys STB island designed for the remote connection of TeSys Model U
starter-controllers and TeSys Quickfit prewired motor-starters.
The application-specific STB EPI 2145 parallel interface comprises:
1 A display block with LEDs for the various states of the starter-controllers
or TeSys Quickfit prewired motor-starters.
2 A location for a customizing label.
3 A color-coded module identification stripe (black).
4 A selection switch used to view each motor-starter state.
5 4 RJ45 connectors for connection of:
b 4 TeSys Model U starter-controllers.
b 4 direct motor-starters with TeSys Quickfit components.
b 2 reversing motor-starters with TeSys Quickfit components.
i.e. 12 inputs and 8 outputs in each of these configurations.
To be ordered separately:
b STB XBA 3000 base width 28.1 mm (1.10"). Includes a place for customizing
labels.
b Optional mechanical keying pins between module and base
of I/O: STB XMP 7700. This device ensures that the module and its base
are properly matched after dismantling or replacement.
b Sheets of customizing labels: STB XMP 7600.
b RJ45 cables between module STB EPI 2145 and each TeSys Model U.
(1) RDY is on permanently if the module is operational. If RDY is not lit, the PDM is not
supplying power. If RDY flashes, the module is faulty.
(2) If ERR is lit or flashing, the module has an internal error.
For information about the signaling of module and channel states, consult the
“System
hardware components reference guide
” included on the CD-ROM STB SUS 8800
or available from our website www.us.telemecanique.com
.
(3) S1: output bank 1 (outputs 1 to 4).
S2: output bank 2 (outputs 5 to 8).
Description
Indication Standard STB EPI 2145 module
Module status (1) Green RDY LED
Module error (2) Red ERR LED
Switch position 4 (3) Green S1 and S2 LEDs
State of outputs Green LEDs O1/5, O2/6, O3/7, O4/8
1
2
5
4
3
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com