Characteristics (continued)
Advantys
STB Distributed I/O
Solution 0
Analog input modules
Detailed characteristics of STB ART 0200 analog input module
Thermocouple range B E J K R S T
Temperature unit
°C or °F (°C by default)
Nominal values
°C (°F) 130 to
1,820 °C
(266 to
3,308 °F)
- 270 to
+ 1,000 °C
(- 518 to
+ 1,832 °F)
- 200 to
+ 760 °C
(- 392 to
+ 1,400 °F)
- 270 to
+ 1,370 °C
(- 518 to
+ 2,498 °F)
- 50 to
+ 1,665 °C
(- 122 to
+ 3,029 °F)
- 50 to
+ 1,665 °C
(- 122 to
+ 3,029 °F)
- 270 to
+ 400 °C
(- 518 to
+ 752 °F)
Resolution
0.1°C or °F
Broken wire detection
Monitored independently on each channel
Conversion time With internal cold-junction
compensation
ms 230 at 50 Hz
210 at 60 Hz
With external cold-junction
compensation
ms 400 at 50 Hz
360 at 60 Hz
Accuracy (thermocouple
errors not included)
With internal cold-junction
compensation
at 25°C
(77°F)
°C (°F) ± 4.6
(40.28)
± 4.6
(40.28)
± 5.1
(41.18)
± 4
(39.2)
± 3.6
(38.48)
± 4.1
(39.38)
± 4.4
(39.92)
at 60°C
(140°F)
°C (°F) ± 6.8
(44.24)
± 6.8
(44.24)
± 7.0
(44.6)
± 5.5
(41.9)
± 4.2
(39.56)
± 5.0
(41)
± 6.4
(43.52)
With external cold-junction
compensation
at 25°C
(77°F)
°C (°F) ± 1.75
(35.15)
at 60°C
(140°F)
°C (°F) ± 2.85
(37.13)
Temperature probe Pt 100 Pt 1000 Ni 100 Ni 1000 Cu 10
Type
2, 3 or 4-wire (3-wire by default)
Temperature unit
°C or °F (°C by default)
Nominal values IEC
°C (°F) -200 to +850 (by default)
(-392 to +1,562)
-60 to +180
(-140 to +356)
-100 to
+ 260
(-212 to
+500
US/JIS
°C (°F) -100 to +450 ( -212 to +842)
Resolution
0.1 °C or °F
Broken wire detection
Monitored independently on each channel
Max. wiring resistance 4-wire
Ω 50 (IEC/US/JIS) 500 (IEC/US/JIS) 50 500 50
2 or 3-wire
Ω 20 (IEC/US/JIS) 200 (IEC/US/JIS) 20 200 20
Conversion time 3-wire
ms 340 at 50 Hz
300 at 60 Hz
2 or 4-wire
ms 200 at 50 Hz
180 at 60 Hz
Accuracy (temperature
probe errors not included)
25°C (77°F) internal
°C (°F) ± 1 (33.8) ± 1 (33.8) ± 4 (39.2)
25°C (77°F) external
°C (°F) ± 2 (35.6) ± 1 (33.8) ± 4 (39.2)
Voltage
Range
mV ± 80 (± 81.92)
Resolution
Increments of 0.01 mV
Conversion time
ms 170 at 50 Hz
150 at 60 Hz
Input impedance
MΩ 10 (standard)
Accuracy 25°C (77°F) internal
% of
full
scale
± 0,1
25°C (77°F) external
% of
full
scale
± 0.15 at ambient temperature
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com