Installation guide
54
Selection guide
Advantys
™
STB Distributed I/O
Solution 0
Analog output modules
Applications Analog output modules
Voltage
Number of channels 2
Range 0...10 V -10…+10 V 0...+ 10 V,
- 10...+ 10 V
Resolution 10 bits 9 bits + sign 11 bits + sign or 12 bits
Load current/channel (outputs) 5 mA
Response time 3 ms for both channels
Acquisition period –
Acquisition or update time 25 ms for both channels
Internal power supply
of 3-wire actuators
Yes
Connections Two STB XTS 1100 screw-type connectors or STB XTS 2100 spring-type connectors (6-
channel)
Base STB XBA 1000
PDM power distribution
modules (1)
Voltage c 24 V
Catalog number STB PDT 3100/3105
Isolation Field-to-bus c 1500 V for 1 minute
Channel-to-channel c 30 V (when actuator voltage is separate from logic bus voltage)
COM fault fallback positions 0 V on 2 channels (2)
Protection against Reverse polarity Yes
Short circuit and overload 2.5 A time-lag fuses recommended on each channel. To be supplied by the user
Electronic protection of
sensor power supply
No Yes
Range Basic Standard
Type of module
STB AVO 1255 STB AVO 1265 STB AVO 1250
Page 62
(1) One PDM (Power Distribution Module) is required per voltage group.
(2) Hold last value: reset to 0 V on both channels; go to a predefined value (between 0 V and full scale) on each channel.
(3) By default, reset to zero on both channels. Each channel individually adjustable: hold the value, go to a predefined value between 0 and 100% of the output range.