Installation guide
19
Characteristics
Advantys
™
STB Distributed I/O
Solution 0
Network Interface Modules
Characteristics
Type of network interface module STB NIP 2212 NCO 2212 NCO 1010 NMP 2212 NFP 2212
Range Standard Standard Basic Standard Standard
Network or bus
Ethernet CANopen Modbus Plus Fipio
Compliance with bus or network standards
IEEE 802.3 CIA DS-301 modbus.org EN 50170, Vol 3, Parts 1-3,
2-3, 3-3, 5-3, 6-3 and 7-3
Power supply
c V 24 not isolated (1)
Input current
mA 700 700 400 700
Voltage limits
c V 19.2…30
Output voltage to the island logic bus
c 5.25 V ± 0.21%
Output current rating
A 1.2
Isolation
None
Immunity to electromagnetic interference (EMC)
Yes, according to IEC 61131-2
Connector type To bus or network
RJ45 female 9-pin SUB-D male 9-pin SUB-D
female
9-pin SUB-D male
RS 232 port (configuration,
dialog with XBT and firmware
update)
HE 13, 8-pin
female
HE 13, 8-pin
female
(2) HE 13, 8-pin female
Max. number of addressable
I/O modules
Per island
32 32 12 32
Number of segments
supported
Primary
1
Extension
up to 6 up to 6 – up to 6
Type of STB network interface module STB NIB 2212 NIB 1010 NDP 2212 NDP 1010 NDN 2212 NDN 1010
Range Standard Basic Standard Basic Standard Basic
Network or bus
INTERBus Profibus DP DeviceNet
Compliance with bus or network standards
INTERBus Club DIN 19245, Parts 1 and 3 Open DeviceNet Vendors
Assoc.
Power supply
c V 24 not isolated (1)
Input current
mA 700 400 700 400 700 400
Voltage limits
c V 19.2…30
Output voltage to the island logic bus
c 5.25 V ± 0.21%
Output current rating
A 1.2
Output impedance
mΩ < 50 to 100
kHz
y 50 < 50 to 100
kHz
y 50 < 50 to 100
kHz
y 50
Isolation
None
Immunity to electromagnetic interference (EMC)
Yes, according to IEC 61131-2
Connector type To bus or network
Input: 9-pin SUB-D male
Output:
9-pin SUB-D female
9-pin SUB-D female 5-pin male connector
RS 232 port (configuration,
dialog with XBT and firmware
update)
HE 13,
8-pin female
(2) HE 13,
8-pin female
(2) HE 13,
8-pin female
(2)
Max. number of addressable
I/O modules
Per island
32 12 32 12 32 12
Number of segments
supported
Primary
1
Extension
up to 6 – up to 6 – up to 6 –
(1) Use a
c
24 V SELV (Safety Extra Low Voltage) external power supply.
(2) Connection for updating firmware only.
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com