Installation guide
15
0
Data exchange between master PLC and Advantys STB I/O modules
Modbus Plus
™
network Fipio
®
bus INTERBUS
®
bus Profibus
DP bus DeviceNet network
Industrial LAN compliant with
the Modbus Plus standard
Open industrial field bus
compliant with the FIP standard
INTERBUS industrial field bus
(Generation 4)
Industrial field bus Profibus
DPV.0
Network compliant with v.2.0
of the Open DeviceNet Vendor
Assoc. (ODVA)
Modbus Plus standard FIP standard Isolated RS 485 RS 485 –
1 Mbit/s 1 Mbit/s 500 Kbit/s 9.6 Kbit/s…12 Mbit/s 125, 250 or 500 Kbit/s
Twisted pair Shielded twisted pair cable Shielded twisted pair cable Shielded twisted pair cable Twisted pair
32 per segment
64 for all segments
32 per segment
Up to 128 for all segments
Up to 512 slaves with up to
254 bus terminal blocks
125 slaves 64 slaves
450 m (492.1 yd) per segment
1800 m (1968.4 yd) with 3
repeaters
1000 m (1093.6 yd) per
segment
400 m (437.4 yd) per bus
segment between stations
12.8 km for the bus between
stations
50 m (54.6 yd) for the
installation bus
1200 m (1312.3 yd) (9.6
Kbit/s),
4800 m (5249.3 yd) with 3
repeaters,
200 m (218.7 yd) (12 Mbit/s),
800 m (874.8 yd) with 3
repeaters
1200 m (1312.3 yd)
Standard NIM: up to 32 modules on 1 primary segment and up to
6 extension segments
Standard NIM: up to 32 modules on 1 primary segment and up to 6 extension segments
Basic NIM: Up to 12 modules on 1 primary segment
Up to 12 devices (2)
- Global data
- Peer-to-peer
- Peer Cop
- Periodic I/O exchanges
- Point-to-Point message
- Use of standard profiles
FRD/FSD/FED
- Implicit process data
exchange ((Data process)
- Logical addressing
- Diagnostics
- Slave configuration
- Configuration control
- Read/write Slave I/O data
- DeviceNet Object (Class ID3)
- Connection Object
(Class ID5)
- Island Bus Object
(Class ID101)
STB NMP 2212 STB NFP 2212 STB NIB 2212 STB NDP 2212 STB NDN 2212
STB NIB 1010 STB NDP 1010 STB NDN 1010
20
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com