Installation guide

14
Selection guide
Advantys
STB Distributed I/O
Solution 0
Network Interface Modules
(1) One Advantys STB island corresponds to 1 device on the bus or the network.
(2) Depending on the nature of the CANopen devices, this maximum number may be limited to 7.
(3) Does not support: the CANopen bus extension module, hot swapping, Advantys software.
Applications Data exchange between master PLC and Advantys STB I/O modules
Bus or network type Ethernet TCP/IP Network CANopen bus
Bus or network nature Industrial LAN CAN field bus
Structure Physical interface 10 BASE-T ISO 1198
Data rate 10 Mbit/s 10 Kbit/s…1 Mbit/s depending on bus length
Medium Shielded dual twisted pair via Ethernet
ConneXium
cabling system
Shielded dual twisted pair
Configuration Number of devices
(1)
Up to 256 per segment,
unlimited with switches
127 slaves
Maximum length 100 m (109.3 yd) according to 802.3 standard
1000 m (1093.6 yd) with ConneXium
cabling
system
> 3000 m (3280.8 yd) with fiber optic
connection
From 30 m (32.8 yd) (1 Mbit/s) to 5,000 m
(5468.0 yd) (10 Kbit/s)
NIM (Network Interface
Module) features
Number of I/O modules per
Advantys STB island (1)
Standard NIM: up to 32 modules on 1 primary
segment and up to 6 extension segments
Standard NIM: up to 32 modules on 1 primary
segment and up to 6 extension segments
Basic NIM: up to 12 modules on 1 primary
segment
Power supply c 24 V not isolated (19.2…30 V)
Logic power supply Provides c 5 V logic power to all the I/O modules of an island (1200 mA)
CANopen devices supported Up to 12 devices (2)
Services used - Embedded Web (configuration, diagnostics,
and access to variables)
- TCP/IP Modbus
- SNMP agent
- DHCP client service
- Process Data Object (PDO)
- Service Data Object (SDO)
- Network management (NMT)
Type of NIM module Standard
STB NIP 2212 STB NCO 2212
Basic (3)
STB NCO 1010
Pages 20