Installation guide
14
Selection guide
Advantys
™
STB Distributed I/O
Solution 0
Network Interface Modules
(1) One Advantys STB island corresponds to 1 device on the bus or the network.
(2) Depending on the nature of the CANopen devices, this maximum number may be limited to 7.
(3) Does not support: the CANopen bus extension module, hot swapping, Advantys software.
Applications Data exchange between master PLC and Advantys STB I/O modules
Bus or network type Ethernet TCP/IP Network CANopen bus
Bus or network nature Industrial LAN CAN field bus
Structure Physical interface 10 BASE-T ISO 1198
Data rate 10 Mbit/s 10 Kbit/s…1 Mbit/s depending on bus length
Medium Shielded dual twisted pair via Ethernet
ConneXium
™
cabling system
Shielded dual twisted pair
Configuration Number of devices
(1)
Up to 256 per segment,
unlimited with switches
127 slaves
Maximum length 100 m (109.3 yd) according to 802.3 standard
1000 m (1093.6 yd) with ConneXium
™
cabling
system
> 3000 m (3280.8 yd) with fiber optic
connection
From 30 m (32.8 yd) (1 Mbit/s) to 5,000 m
(5468.0 yd) (10 Kbit/s)
NIM (Network Interface
Module) features
Number of I/O modules per
Advantys STB island (1)
Standard NIM: up to 32 modules on 1 primary
segment and up to 6 extension segments
Standard NIM: up to 32 modules on 1 primary
segment and up to 6 extension segments
Basic NIM: up to 12 modules on 1 primary
segment
Power supply c 24 V not isolated (19.2…30 V)
Logic power supply Provides c 5 V logic power to all the I/O modules of an island (1200 mA)
CANopen devices supported Up to 12 devices (2)
Services used - Embedded Web (configuration, diagnostics,
and access to variables)
- TCP/IP Modbus
- SNMP agent
- DHCP client service
- Process Data Object (PDO)
- Service Data Object (SDO)
- Network management (NMT)
Type of NIM module Standard
STB NIP 2212 STB NCO 2212
Basic (3)
STB NCO 1010
Pages 20